© Siemens AG 2010 Solid-State Switching Devices for Resistive Loads Solid-State Relays General data Overview Solid-State Relays Three-phase solid-state relays with a width of 45 mm SIRIUS solid-state relays are suitable for surface mounting on existing cooling surfaces. Mounting is quick and easy, involving just two screws. The special technology of the power semicon- ductor ensures there is excellent thermal contact with the heat sink. Depending on the nature of the heat sink, the capacity reaches up to 88 A on resistive loads. With its compact design and a width of just 45 m, which stays the same even at currents of up to 55 A, the 3RF22 solid-state relay offers an ultra small footprint.
The logical connection method, with the power infeed from above and load connection from be- low, ensures tidy installation in the control cabinet. The three-phase solid-state relays are available with • two-phase control (suitable in particular for circuits without connection to the neutral conductor) and • three-phase control (suitable for star circuits with connection to the neutral conductor or for applications in which the system requires all phases to be switched). The solid-state relays are available in three different versions:
• 3RF21 single-phase solid-state relay with a width of 22.5 mm • 3RF20 single-phase solid-state relay with a width of 45 mm • 3RF22 three-phase solid-state relay with a width of 45 mm The 3RF21 and 3RF22 solid-state relays can be expanded with various function modules to adapt them to individual applica- tions. Selection notes When selecting solid-state relays, in addition to information about the network, the load and the ambient conditions it is also necessary to know details of the planned design. The solid-state relays can only conform to their specific technical specifications if they are mounted with appropriate care on an adequately di- mensioned heat sink.
4 Version for resistive loads, "zero-point switching" This standard version is often used for switching space heaters on and off. In this version the solid-state relay is specifically matched to in- ductive loads. Whether it is a matter of frequent actuation of the valves in a filling plant or starting and stopping small operating mechanisms in packet distribution systems, operation is carried out safely and noiselessly. Version for inductive loads, "instantaneous switching" The following procedure is recommended:
• Determine the rated current of the load and the mains voltage • Select the relay design and choose a solid-state relay with higher rated current than the load • Determine the thermal resistance of the proposed heat sink • Check the correct relay size with the aid of the diagrams Special "Low noise" version Thanks to a special control circuit, this special version can be used in public networks up to 16 A without any additional mea- sures, such as interference suppressor filters. As a result, in terms of emitted interference, it conforms to limit value curve class B according to EN 60947-4-3. You can find more information on the Internet at:
www.siemens.com/solid-state-switching-devices Single-phase solid-state relays with a width of 22.5 mm With its compact design and a width of just 22.5 mm, which stays the same even at currents of up to 88 A, the 3RF21 solid-state relay offers an ultra small footprint. The logical connection method, with the power infeed from above and load connection from below, ensures tidy installation in the control cabinet. Single-phase solid-state relays with a width of 45 mm The solid-state relays with a width of 45 mm provide for connec- tion of the power supply lead and the load from above. This makes it easy to replace existing solid-state relays in existing ar- rangements.
The connection of the control cable also saves space in much the same way as the 22.5 mm design, as it is sim- ply plugged on. 4/48 Siemens LV 1 · 2010