Siemens — Siemens SIRIUS 3RW Soft Starters and Solid-State Switching Devices Manual

© Siemens AG 2010 Solid-State Switching Devices for Resistive Loads General data Notes on integration in the load feeders Alternatively, if there is lower loading, protection can also be pro- vided by standard fuses or miniature circuit breakers. This pro- tection is achieved by overdimensioning the solid-state switch- ing devices accordingly. The technical specifications and the product data sheets contain details both about the solid-state fuse protection itself and about use of the devices with conven- tional protection equipment. The SIRIUS solid-state switching devices are very easy to inte- grate into the load feeders thanks to their industrial connection method and design.

Particular attention must however be paid to the circumstances of the installation and ambient conditions, as the performance of the solid-state switching devices is largely dependent on these. Depending on the version, certain restrictions must be ob- served. Detailed information, for example in relation to solid- state contactors about the minimum spacing and to solid-state relays about the choice of heat sink, is given in the technical specifications (see manual) and the product data sheets. Electromagnetic compatibility (EMC) The solid-state switching devices are suitable for interference- free operation in industrial networks without further measures.

If they are used in public networks, it may be necessary for con- ducted interference to be reduced by means of filters. For applications with a very large power requirement it is possi- ble to use SIVOLT AC power controller. More information on the product range can be found in the Catalog DA 68 or in our Mall. This does not include the solid-state contactors for resistive loads of the special type 3RF23..-.CA.. "Low Noise". These com- ply with the class B limit values up to a rated current of 16 A. If other versions are used, and at currents of over 16 A, standard filters can be used in order to comply with the limit values.

The decisive factors when it comes to selecting the filters are essen- tially the current loading and the other parameters (operational voltage, design type, etc.) in the load feeder. See ID: 10752358 support.automation.siemens.com/WW/view/de/10862346 Short-circuit and overload protection 4 Despite the rugged power semiconductors that are used, solid- state switching devices respond more sensitively to short-cir- cuits in the load feeder. Consequently, special precautions have to be taken against destruction, depending on the type of de- sign. Suitable filters can be ordered from EPCOS AG. You can find more information on the Internet at:

www.epcos.com Siemens generally recommends using SITOR semiconductor protection fuses. These fuses also provide protection against destruction in the event of a short-circuit even when the solid- state contactors and solid-state relays are fully utilized. 4/47 Siemens LV 1 · 2010