© Siemens AG 2010 Solid-State Switching Devices for Resistive Loads General data Application Applications The powerful SIRIUS solid-state relays and contactors can be used to control several heating loads at the same time. By using a load monitoring module the individual partial loads can easily be monitored, and in the event of a failure a signal is generated to be sent to the controller. Example: Plastics processing industry Thanks to their high switching endurance, SIRIUS solid-state switching devices are ideally suited for use in the control of elec- trical heat. This is because the more precise the temperature regulation process has to be, the higher the switching frequency.
The accurate regulation of electrical heat is used for example in many processes in the plastics processing industry: • Band heaters heat the extrudate to the correct temperature in plastic extruders • Heat emitters heat plastic blanks to the correct temperature • Heat drums dry plastic granules • Heating channels keep molds at the correct temperature in or- der to manufacture different plastic parts without defects Use in fuseless load feeders Short-circuit protection and line protection with miniature circuit breakers is easy to achieve with SIRIUS solid-state relays and solid-state contactors in comparison with designing load feed- ers with fuses.
A special version of the solid-state contactors can be protected against damage in the case of a short-circuit with a miniature circuit breaker with type B tripping characteristic. This allows the low-cost and simple design of fuseless load feed- ers with full protection of the switchgear. 4 More information Specification 1) Please contact Technical Assistance. 2) "Low Noise" version for residential, business and commercial applications up to 16 A, AC-51. 3) These products were built as Class A devices. The use of these devices in residential areas could result in lead in radio interference. In this case these may be required to introduce additional interference suppression measures.
4/46 Siemens LV 1 · 2010 Type 3RF20, 3RF21, 3RF23 ..-.A..., -.B..., -.D... 3RF23 ..-.C... 3RF22, 3RF24 General data Ambient temperature • During operation, derating from 40 °C °C • During storage °C -25 ... + 60 -55 ... + 80 Installation altitude m 0 ... 1000; derating from 10001) Shock resistance g/ms acc. to IEC 60068-2-27 15/11 Vibration resistance g acc. to IEC 60068-2-6 2 Degree of protection IP20 Insulation strength at 50/60 Hz V rms (main/control circuit to floor) 4000 Electromagnetic compatibility (EMC) • Emitted interference - Conducted interference voltage acc. to IEC 60947-4-3 - Emitted, high-frequency interference voltage acc.
to IEC 60947-4-3 • Interference immunity - Electrostatic discharge kV acc. to IEC 61000-4-2 (corresponds to degree of severity 3) - induced RF fields MHz acc. to IEC 61000-4-6 - Burst acc. to IEC 61000-4-4 kV - Surge acc. to IEC 61000-4-5 kV Class A for industrial applications Class A for industrial applications Class B for residential applications2) Class A for industrial applications3) Class A for industrial applications Class A for industrial applications Class A for industrial applications Contact discharge: 4; Air discharge: 8; Behavior criterion 2 0.15 ... 80; 140 dBμV; behavior criterion 1 2/5.0 kHz; behavior criterion 1 Conductor - Ground: 2; Conductor - Conductor:
1; Behavior criterion 2 Permissible mounting positions ±10° ±10° NSB0_01703