Siemens — Siemens BETA Low-Voltage Circuit Protection Manual

© Siemens AG 2010 BETA Protecting Overvoltage Protection Devices Combination surge arresters, type 1 and type 2 Overview Benefits Type 1 and type 2 combination surge arresters protect low-volt- age systems against the overvoltages and high currents that can be triggered by direct lightning strikes. They are tested by wave- shaped lightning impulses, 25 ... 100 kA with waveform 10/350 μs. The rated arrester voltage is a uniform 350 V AC. This in- creases safety in systems with extended voltage overshoots. All combination surge arresters are fitted with a mechanical fault indication that does not require an extra power supply. The protective modules are plug-in versions.

No dismantling of electrical wires required when replacing the protective modules. When taking insulation measurements, the protec- tive modules are simply removed, in order to ensure discon- nection from the power supply. The same type 2 overvoltage protective modules are used as for the slim version of the surge arresters (5SD7 42.). This sim- plifies stock keeping. All combination surge arresters have a remote signaling con- tact, which signals if the device fails. The protection level is lowered to 1.5 kV by the combination surge arresters. A thermal isolating arrester disconnector offers a high degree of protection against overload. All spark gaps are triggered.

For this reason, decoupling reac- tors are no longer required for the installation of overvoltage pro- tection devices. Selection and ordering data 19 19/123 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof. Version Discharge MW DT capacity kA Order No. Price per PU PU PS* PG Weight per PU approx. Unit(s) Unit(s) kg Weight per PU approx.

Combination surge arresters 1P 25 2 A For single-conductor systems with remote signaling 2P 100 4 B For TN-S and TT systems with remote signaling 3P 75 6 A For TN-C systems with remote signaling 4P 100 8 A For TN-S and TT systems with remote signaling 1 1 008 0.356 5SD7 441-1 5SD7 442-1 1 1 008 0.770 5SD7 443-1 1 1 008 1.040 5SD7 444-1 1 1 008 1.430