Siemens — Siemens BETA Low-Voltage Circuit Protection Manual

© Siemens AG 2010 BETA Protecting Overvoltage Protection Devices Surge arresters, type 2 Overview Benefits Surge arresters type 2 are used after lightning arresters type 1 in main distribution boards or sub-distribution boards. They protect low-voltage systems against transient overvoltages. The rated arrester voltage is a uniform 350 V AC. This in- creases safety in systems with extended voltage overshoots. All type 2 surge arresters are fitted with a mechanical fault in- dication that does not require an extra power supply A thermal isolating arrester installed in each device offers a high degree of protection.

In the event of overload, the surge arrester is disconnected from the mains - the plant continues running. The protective modules are plug-in versions. No dismantling of electrical wires required when replacing the protective modules. When taking insulation measurements, the protec- tive modules are simply removed in order to disconnect from the power supply. All surge arresters are available with a remote signaling con- tact, which signals if the device fails. The type 2 surge arrester lowers the protection level to 1.4 to 1.5 kV.

A remote signaling contact indicates whether a protective module has been disconnected from the network by the thermal arrester disconnector or whether it is just not plugged in. All spark gaps are triggered. For this reason, decoupling reac- tors are no longer required for the installation of overvoltage pro- tection devices. To ensure fault-free operation of photovoltaic systems, it is es- sential to have standardized protection against lightning and ov- ervoltages. SPDs (5SD7 483-.) for the DC side protect the pho- tovoltaic generator and the inverter against overvoltages. The SPDs 5SD7 473-. and 5SD7 485-. are available specially for the protection of IT systems.

19 19/124 Siemens LV 1 · 2010