© Siemens AG 2010 BETA Protecting Residual Current Protective Devices Additional components Overview Benefits Auxiliary switches (AS) signal the contact position of the RCCB. Using captive brackets, the remote-controlled mechanism can be attached (or retroffitted) to the right-hand side of the basic device without the need for tools Bus systems, such as instabus KNX, AS-Interface bus or PROFIBUS, can be integrated in the communication over bi- nary inputs The leakage current measurement device enables the sys- tematic selection of the rated residual current, thus helping to prevent the inadvertent tripping of RCCBs.
Remote-controlled mechanisms are used for the remote ON/OFF switching of RCCBs. They also enable local manual switching. A blocking function permits maintenance work. If the RCCB is tripped, an acknowledgment must be carried out prior to switch- ing back on. The leakage current measurement device detects the leakage currents - like the circuit breaker - thus providing a direct state- ment as to the current loading of the RCCB. It is used to measure leakage currents up to 300 mA. This requires a voltmeter with an internal resistance more than 1 M /V and a measuring range for AC voltages of U eff = 1 mV to 2 V.
For the fault-free operation of an RCCB, the measured leakage current should be no greater than 1/3 of the rated residual current. Selection and ordering data 19 * You can order this quantity or a multiple thereof. 19/54 Siemens LV 1 · 2010 Version MW DT Order No. Price per PU PU PS* PG Weight per PU approx. Unit(s) Unit(s) kg Weight per PU approx. Auxiliary switches (AS) For 5SM3 RCCBs up to 80 A 1 NO + 1 NC 0.5 } 2 NC 0.5 C 2 NO 0.5 A 1 1/10 008 0.042 1 1/10 008 0.042 1 1/10 008 0.042 5SW3 300 5SW3 301 5SW3 302 Auxiliary switches (AS) For 5SM3 RCCBs, 100 ...
125 A, 3P+N 1 NO + 1 NC 0.5 B 1 1 008 0.040 5SW3 330 Remote-controlled mechanisms (RC) For 5SM3 RCCBs up to 80 A Rated voltage Un = 230 V AC 3.5 B 1 1 027 0.395 5ST3 051 Leakage current measurement device Rated voltage Un = 500 V AC; 4 B 50 ... 60 Hz, 4P Rated residual current In = 0 ... 300 mA Rated current In = 63 A 1 1 008 0.430 5SM1 930-0 Covers for connection terminals For residual current operated circuit breakers up to 80 A, sealable (2 units in plastic bag) I2_13711a 2 A 2.5 A 4 A 1 1/50 008 0.003 1 1/50 008 0.004 1 1/50 008 0.006 5SW3 010 5SW3 011 5SW3 008