© Siemens AG 2010 BETA Protecting Residual Current Protective Devices Additional components RC units, type A, 5SM2 More information Gossen-Metrawatt offers suitable test devices for RCCB function tests and for testing protective measures. Gossen-Metrawatt GmbH Thomas-Mann-Str. 16-20 D-90471 Nuremberg Germany Tel. +49 (0) 9 11/86 02-111 Fax +49 (0) 9 11/86 02-777 www.gmc-instruments.com E-mail: info@gmc-instruments.com Information is available at:

Overview Benefits RC units, type A, 5SM2 Our wide variety of RC unit types and comprehensive range of miniature circuit breakers offer a huge spectrum of combina- tions for all applications All devices have an current withstand capability of more than 1 kA, thus ensuring safe and reliable operation All additional components for miniature circuit breakers can be retrofitted on the right-hand side All 100 A and 125 A RC units offer external remote tripping over terminals Y1/Y2. This supports implementation of central OFF circuits Both components can be simply plugged into each other and secured with captive metal brackets - no tools required. This saves considerable time when mounting.

RC units of type A can be used in all systems up to 240/415 V AC. They trip in the event of both sinusoidal AC fault currents and pulsating DC residual currents. RCCBs with a rated residual current of maximum 30 mA are used for personnel, material and fire protection, and for addi- tional protection against direct contact. Devices with a rated residual current of maximum 300 mA are used as preventative fire protection in case of insulation faults. RC units are combined with MCBs with characteristics A, B, C and D, provided that these are available in the MCB range. The two components are simply plugged together without the need for any tools.

They then form a combination of RCCB and MCB for personnel, fire and line protection. Super resistant ж Super resistant (short-time delayed) RC units satisfy the maxi- mum permissible break times for instantaneous devices. How- ever, by implementing a short-time delay they prevent unneces- sary trippings, and thus plant faults, when pulse-shaped leakage currents occur - as is the case when capacitors are switched on. Selective о Can be used as upstream group switch for selective tripping contrary to a downstream, instantaneous or super resistant RCCB. 19 The dimensioning of the rated residual current depends on the size of the plant.

19/55 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof. Version MW DT Order No. Price per PU PU PS* PG Weight per PU approx. Unit(s) Unit(s) kg Weight per PU approx. Locking devices for RCCBs up to 80 A, sealable and lockable 4.5 mm hole diameter B 1 10 008 0.008 5SW3 303 Padlocks For 5SW3 303 locking device } 1 1 027 0.027 5ST3 802 Locking devices with padlock Comprising 5SW3 303 locking device and B 5ST3 802 padlock 1 set 1 set 008 0.035 5SW3 312