© Siemens AG 2010 BETA Protecting Low-Voltage Fuse Systems 3NW. ...-0HG Class CC fuse systems Overview Benefits Class CC fuses are used for "branch circuit protection". For switchgear assemblies and mechanical engineers who export their plants. Compliance with the American standard is as follows: Approved according to UL and CSA for typical "Branch Circuit Protection" applications. This facilitates export. Modern design with touch protection to BGV A3 ensures safe installation. The encapsulated fuse holders are tested and designed to the US National Electrical Code NEC 210.20(A) so that in uninter- rupted duty only 80 % of the rated current is permitted as oper- ational current.

An operational current of 100 % of the rated current (30 A) is only permitted short-time. The devices are prepared for the inscription labels of the ALPHA FIX terminal blocks 8WH8 120-7AA15 and 8WH8 120-7XA05. There are three different series: Characteristic slow: 3NW1 ...-0HG For the protection of control transformers, reactors, induc- tances. Significantly slower than the minimum requirements of 12 s at 2 Ч I n as specified by UL for Class CC fuses. Characteristic quick: 3NW2 ...-0HG For a wide range of applications, for the protection of lighting installations, heating, control systems. Characteristic slow: current-limiting 3NW3 ...-0HG slow for overloads and quick for short circuits.

High current limiting for the protection of motor circuits. Selection and ordering data Class CC fuse links 0.6 (6/10) C 018 1 10 0.008 0.8 (8/10) C 018 1 10 0.008 1 C 018 C 1 10 018 0.008 1.5 (1 Ѕ) C 018 1 10 0.008 2 C 018 C 1 10 018 0.008 3 C 018 C 1 10 018 0.008 4 C 018 C 1 10 018 0.008 5 C 018 C 1 10 018 0.008 6 C 018 C 1 10 018 0.008 8 C 018 C 1 10 018 0.008 10 C 018 C 1 10 018 0.008 12 C 1 10 018 0.008 15 C 018 C 1 10 018 0.008 20 C 018 C 1 10 018 0.008 25 C 018 C 1 10 018 0.008 30 C 018 1 10 0.008 19 19/79 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof. Number of poles Un In MW DT V A Order No. Price per PU PU PS* PG Weight per PU approx.

Unit(s) Unit(s) kg Weight per PU approx. Class CC fuse holders 1P 600 30 1 C 2P 600 30 2 C 3P 600 30 3 C 1 12 018 0.056 1 6 018 0.118 1 4 018 0.172 3NW7 513-0HG 3NW7 523-0HG 3NW7 533-0HG In1) DT A Characteristic: slow PG DT Characteristic quick PU PS* PG Weight per PU approx. Unit(s) Unit(s) kg Order No. Price per PU Order No. Price per PU Weight per PU approx.

3NW1 006-0HG 3NW1 008-0HG 3NW1 010-0HG 3NW1 015-0HG 3NW1 020-0HG 3NW1 030-0HG 3NW1 040-0HG 3NW1 050-0HG 3NW1 060-0HG 3NW1 080-0HG 3NW1 100-0HG -- 3NW1 150-0HG 3NW1 200-0HG 3NW1 250-0HG 3NW1 300-0HG -- -- 3NW2 010-0HG -- 3NW2 020-0HG 3NW2 030-0HG 3NW2 040-0HG 3NW2 050-0HG 3NW2 060-0HG 3NW2 080-0HG 3NW2 100-0HG 3NW2 120-0HG 3NW2 150-0HG 3NW2 200-0HG 3NW2 250-0HG --