© Siemens AG 2010 BETA Protecting Low-Voltage Fuse Systems 3NX1 LV HRC signal detectors Overview LV HRC (NH type) signal detectors are used for remotely indicat- ing that the LV HRC fuse links have been tripped. Three different solutions are available: 3NX1 021 signal detectors with signal detector links The LV HRC signal detectors with signal detector link support monitoring of LV HRC fuse links with non-insulated grip lugs of sizes 000 to 4 at 10 A or more. The signal detector link is connected in parallel to the LV HRC fuse link. In the event of a fault, the LV HRC fuse links are re- leased simultaneously with the fuse signaling link. A tripping pin switches a floating microswitch.

3NX1 024 signal detector top The signal detector top can be used with LV HRC fuse links, sizes 000, 00, 1 and 2, which are equipped with non-insulated grip lugs and have a front indicator or combination alarm. It is simply plugged into the grip lugs. 5TT3 170 fuse monitors If a fuse is tripped, the front indicator springs open and switches a floating microswitch. This solution should not be used for safety-relevant plants. For this purpose, we recom- mend our electronic fuse monitors. Benefits Uniform solution for all sizes LV HRC signal detectors reliably indicate when a fuse has tripped. Tripped fuses are quickly located. This saves time and increases plant availability.

The LV HRC signal detector top is a cost-effective solution for monitoring Siemens LV HRC fuse links of sizes 000, 00, 1 and 2. LV HRC fuse link % LV HRC signal detec- tors & Microswitch 6 I2_13744 ( Spring contact % ) Hinged lid * Signal detector links 1 5 ( 4 2 3 & Selection and ordering data 19 * You can order this quantity or a multiple thereof. 19/94 Siemens LV 1 · 2010 $ LV HRC fuse link % Front indicator & Signal detector tops ( Rocker/lever arm Size DT Order No. Price per PU PU PS* PG Weight per PU approx. Unit(s) Unit(s) kg Weight per PU approx.

LV HRC signal detectors 000 to 4 A Only for SIEMENS 3NA3, 3NA7 and 3ND LV HRC fuse links with non-insulated grip lugs • Rated voltage up to 690 V AC/600 V DC • Contact: microswitch 250 V AC, 6 A • Connection: flat termination 2.3 mm 3NX1 021 1 1 014 0.036 Signal detector links 000 to 4 • Rated voltage up to 690 V AC/ 600 V DC Response value > 9 V; 2.5 A; A for standard applications Response value > 2 V; 7 A; C only for meshed systems 1 3 014 0.015 1 3 014 0.015 3NX1 022 3NX1 023 Signal detector tops 000, 00, 1, 2 } Only for SIEMENS 3NA3, 3NA7 and 3ND LV HRC fuse links with non-insulated grip lugs • Rated voltage up to 690 V AC/600 V DC • Contact: microswitch 230 V AC, 5 A, 1 CO • Connection:

flat termination 2.3 mm 3NX1 024 1 1 014 0.010