Manual - BMV-700H The "clear relay" value needs to be greater than the "set relay" value. When the "set relay" and "clear relay" values are equal, the state of charge condition will be unable to drive the relay. Note that this setting is also known as the discharge floor. The time-to-go reading displayed by the battery monitor relates to this setting. The time to go is the time left until this setting (the discharge floor) has been reached. 7.3.7. Low voltage relay When the battery voltage falls below the "set relay" value for more than 10 seconds the relay will close.
When the battery voltage rises above the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [27] and/or the Relay off delay [27] settings). The "clear relay" value needs to be greater than the "set relay" value. When the battery voltage rises above the "set relay" value for more than 10 seconds the relay will close. 7.3.8. High voltage relay When the battery voltage falls below the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [27] and/or the Relay off delay [27] settings). The "clear relay" value needs to be greater than the "set relay" value. 7.4.
Alarm settings The BMV battery monitor is equipped with an alarm relay and a buzzer. Alarms are also visible on the VictronConnect app while connected to the battery monitor or are used to send an alarm signal to a GX device. Alarms are disabled by default. To enable do the following: In the VictronConnect app, enable the alarm by sliding the slider button to the right. Via the head unit, enable the alarm by changing the "set" and "clear" value in the alarm settings to any value above zero. 7.4.1. Alarm buzzer When enabled (set to ON), the buzzer will sound an alarm as soon as an alarm condition occurs. After a button is pressed, the buzzer will stop sounding.
When disabled (set to OFF) the buzzer will not sound an alarm. Page 28 All features and settings Setting Default Range Step size Set relay value (setting 16) 50% 0 - 99% 1% Clear relay value (setting 17) 90% 0 - 99% 1% Setting Default Range Step size Set relay value (setting 18) 0V 0 - 384V 0.1V Clear relay value (setting 19) 0V 0 - 384V 0.1V Setting Default Range Step size Set relay value (setting 20) 0V 0 - 384V 0.1V Clear relay value (setting 21) 0V 0 - 384V 0.1V Setting Default Modes Alarm buzzer (setting 32) ON ON OFF