Victron BMV-712 Smart — 7.2.5. Charged detection time

Manual - BMV-712 Smart The maximum battery capacity of 32500Ah is supported from firmware version v4.19 onwards; lower versions support a maximum of 9999Ah. 7.2.2. Charged voltage The battery voltage must be above this voltage level to consider the battery as fully charged. As soon as the battery monitor detects that the voltage of the battery has reached this “charged voltage” parameter and the current has dropped below the “ tail current [29] ” parameter for the duration of the “ charged detection time [29] ” parameter, the battery monitor will set the state of charge to 100%. The table below indicates the recommended settings per battery type. 7.2.3.

Discharge floor The “Discharge floor” parameter is used in the "time remaining" calculation. The battery monitor calculates the time it takes until the set “ discharge floor [29] ” has been reached. It is also used to set the state of charge alarm defaults. For lead-acid batteries set this to 50% and for lithium set it lower. Note that this setting only appears when accessing the battery monitor via the VictronConnect app. In case the battery monitor is accessed via the head unit, see the Low State of Charge (SoC) relay [33] setting instead. 7.2.4. Tail current The battery is considered as fully charged once the charge current has dropped to less than this “Tail current” parameter.

The “Tail current” parameter is expressed as a percentage of the battery capacity. Note that some battery chargers stop charging when the current drops below a set threshold. In these cases, the tail current must be set higher than this threshold. As soon as the battery monitor detects that the voltage of the battery has reached the set “ Charged voltage [29] ” parameter and the current has dropped below this “Tail current” parameter for a certain amount of time, the battery monitor will set the state of charge to 100%. 7.2.5.

Charged detection time This is the time the “ Charged voltage [29] ” parameter and the “ Tail current [29] ” parameter must be met in order to consider the battery fully charged.

Page 29 All features and settings Setting Default Range Step size Charged voltage (setting 02) 14.0V (12V nominal) 28.0V (24V nominal) 56.0V (48V nominal) 0 - 70V 0.1V Nominal battery voltage Charged voltage setting Lithium Lead-acid 12V 13.9V 14.0V 24V 27.8V 28.0V 36V 41.7V 42.0V 48V 55.6V 56.0V Setting Default setting Range Step size Discharge floor 50% 0 - 99% 1% Setting Default Range Step size Tail current (setting 03) 4.00% 0.50 - 10.00% 0.1% Setting Default setting Range Step size Charged detection time (setting 04) 3 minutes 0 - 100 minutes 1 minute