Victron BMV-712 Smart — 7.2.10. Battery SOC on reset

Manual - BMV-712 Smart 7.2.6. Peukert exponent Set the Peukert exponent parameter according to the battery specification sheet. If the Peukert exponent is unknown, set it at 1.25 for lead-acid batteries and set it at 1.01 for lithium batteries. A value of 1.00 disables the Peukert compensation. The Peukert value for lead-acid batteries can be calculated. For more information on the Peukert calculation, the Peukert exponent and how this relates to the battery capacity, see the Battery capacity and Peukert exponent [44] chapter. 7.2.7. Charge efficiency factor The “Charge Efficiency Factor” compensates for the capacity (Ah) losses during charging.

A setting of 100% means that there are no losses. A charge efficiency of 95% means that 10Ah must be transferred to the battery to get 9.5Ah actually stored in the battery. The charge efficiency of a battery depends on battery type, age and usage. The battery monitor takes this phenomenon into account with the charge efficiency factor. The charge efficiency of a lead acid battery is almost 100% as long as no gas generation takes place. Gassing means that part of the charge current is not transformed into chemical energy, which is stored in the plates of the battery, but is used to decompose water into oxygen and hydrogen gas (highly explosive!).

The energy stored in the plates can be retrieved during the next discharge, whereas the energy used to decompose water is lost. Gassing can easily be observed in flooded batteries. Please note that the ‘oxygen only’ end of the charge phase of sealed (VRLA) gel and AGM batteries also results in a reduced charge efficiency. 7.2.8. Current threshold When the current measured falls below the “Current threshold” parameter it will be considered zero. The “Current threshold” is used to cancel out very small currents that can negatively affect the long-term state of charge readout in noisy environments.

For example, if the actual long-term current is 0.0A and, due to injected noise or small offsets, the battery monitor measures 0.05A the battery monitor might, in the long term, incorrectly indicate that the battery is empty or will need to be recharged. When the current threshold in this example is set to 0.1A, the battery monitor calculates with 0.0A so that errors are eliminated. A value of 0.0A disables this function. 7.2.9. Time-to-go averaging period The time-to-go averaging period specifies the time window (in minutes) that the moving averaging filter works. A value of 0 (zero) disables the filter and gives an instantaneous (real-time) readout.

However, the displayed “Time remaining” value may fluctuate heavily. Selecting the longest time, 12 minutes, will ensure that only long-term load fluctuations are included in the “Time remaining” calculations. 7.2.10. Battery SOC on reset Note that if you access this setting through the head unit, this setting will be categorized under "Miscellaneous settings". However, when accessed via the VictronConnect app, it falls under "Battery settings". This setting determines the behaviour of the state of charge (SOC) value following a battery monitor reset. A reset occurs when the battery monitor is powered down and subsequently powered up again.

This occurs during initial installation or disconnection, such as on a boat when the DC system is disconnected via the main DC breaker. The "Battery SOC on reset" setting has the following modes: Keep SOC - The state of charge is set to its last known value. This is the default mode. In this mode, the battery monitor regularly stores the state of charge and, after losing power, resumes from the last known state of charge. Clear - The state of charge remains unknown until the synchronization levels are reached and synchronization occurs.

Page 30 All features and settings Setting Default Range Step size Peukert exponent (setting 05) 1.25 1.00 - 1.50 0.01 Setting Default setting Range Step size Charge efficiency factor (setting 06) 95% 50 - 100% 1% Setting Default Range Step size Current threshold (setting 07) 0.10A 0.00 - 2.00A 0.01A Setting Default Range Step size Time-to-go averaging period (setting 08) 3 minutes 0 - 12 minutes 1 minute