MG.50.A4.50 - VLT является зарегистрированной торговой маркой Danfoss 174 VLT cåðèè 5000 PNU # Parameter Factory setting Range Online 4-Setup Conversion Data index type description 001 Language English Yes No 0 5 002 Local/remote control Remote control Yes Yes 0 5 003 Local reference 000.000 Yes Yes -3 4 004 Active setup Setup 1 Yes No 0 5 005 Programming setup Active setup Yes No 0 5 006 Copying of setups No copying No No 0 5 007 LCP copy No copying No No 0 5 008 Display scaling of motor frequency 1 0.01 - 100.00 Yes Yes -2 6 009 Display linie 2 Frequency [Hz] Yes Yes 0 5 010 Display line 1.1 Reference [%] Yes Yes 0 5 011 Display line 1.2 Motor current [A] Yes Yes 0 5 012 Display line 1.3 Power [kW] Yes Yes 0 5 013 Local control/configura LCP digital control/as par.100 Yes Yes 0 5 014 Local stop Possible Yes Yes 0 5 015 Local jog Not possible Yes Yes 0 5 016 Local reversing Not possible Yes Yes 0 5 017 Local reset of trip Possible Yes Yes 0 5 018 Lock for data change Not locked Yes Yes 0 5 019 Operating state at power-up, local control Forced stop, use saved ref.
Yes Yes 0 5 100 Configuration Speed regulation, open loop No Yes 0 5 101 Torque characteristics High - constant torque Yes Yes 0 5 102 Motor power Depends on the unit 0.18-250 kW No Yes 1 6 103 Motor voltage Depends on the unit 200 - 500 V No Yes 0 6 104 Motor frequency 50 Hz No Yes 0 6 105 Motor current Depends on the unit 0.01-I VLT,MAX No Yes -2 7 106 Rated motor speed Depends on the unit 100-60000 rpm No Yes 0 6 107 Automatic motor adaptation, AMA Adaptation off No No 0 5 108 Stator resistor Depends on the unit No Yes -4 7 109 Stator reactance Depends on the unit No Yes -2 7 110 Motor magnetizing, 0 rpm 100 % 0 - 300 % Yes Yes 0 6 111 Min.
frequency normal magnetizing 1.0 Hz 0.1 - 10.0 Hz Yes Yes -1 6 112 113 Load compensation at low speed 100 % 0 - 300 % Yes Yes 0 6 114 Load compensation at high speed 100 % 0 - 300 % Yes Yes 0 6 115 Slip compensation 100 % -500 - 500 % Yes Yes 0 3 116 Slip compensation time constant 0.50 s 0.05 - 1.00 s Yes Yes -2 6 117 Resonance dampening 100 % 0 - 500 % Yes Yes 0 6 118 Resonance dampening time constant 5 ms 5 - 50 ms Yes Yes -3 6 119 High starting torque 0.0 sec. 0.0 - 0.5 s Yes Yes -1 5 120 Start delay 0.0 sec. 0.0 - 10.0 s Yes Yes -1 5 121 Start function Coasting in start delay time Yes Yes 0 5 122 Function at stop Coasting Yes Yes 0 5 123 Min.
frequency for activating function at stop 0.0 Hz 0.0 - 10.0 Hz Yes Yes -1 5 124 DC holding current 50 % 0 - 100 % Yes Yes 0 6 125 DC braking current 50 % 0 - 100 % Yes Yes 0 6 126 DC braking time 10.0 sec. 0.0 - 60.0 sec. Yes Yes -1 6 127 DC brake cut-in frequency Off 0.0-par. 202 Yes Yes -1 6 128 Motor thermal protection No protection Yes Yes 0 5 129 External motor fan No Yes Yes 0 5 130 Start frequency 0.0 Hz 0.0-10.0 Hz Yes Yes -1 5 131 Initial voltage 0.0 V 0.0-par. 103 Yes Yes -1 6