EN 4.4.1. Connecting Power The following hardware is rated for operation with 110/240 VAC supply: PR-6AC, PR-12AC, PR-14AC, PR-18AC, PR-24AC and PR-E-16AC The following hardware is rated for operation with Figure 15 PR-24 Wall Mountings 12/24 VDC supply: PR-6DC, PR-12DC, PR-14DC, PR-18DC, PR-24DC and PR-E-16DC NOTICE: A power failure may cause an additional edge triggering signal. Only data from the last uninterrupted cycle will be stored. Figure 16 PR-12-N Wall Mountings Wiring Use a screwdriver with a 3-mm blade or adjusting Rievtech hardware terminals. You do not need wire ferrules for the terminals. You can use conductors with cross-sections of up to the following thicknesses:
1 x 2.5 mm 2 2 x 1.5 mm 2 for each second terminal chamber Tightening torque: 0.4... .0.5 N/m (3. .4 lbs/in) Figure 17 Power Connection NOTICE: Always cover the terminals after you have completed the installation. To protect against accidental contact with live parts. Local electrical standards must be complied with. Programmable Relay ● User Manual for ELC, EXM and PR Series 47 2020 v6.0 ● © Rievtech Co.,