xiaomi — Micro PLC User Manual v6.0 1

EN 4.4.2. Connecting Input Signals Inputs can be connected to various sensor elements such as momentary switches, switches, light barriers, daylight control switches, etc. Table 10 Input Status NOTICE: For PR-6DC-DA-R, PR-12DC-DA, PR-14DC-DA, PR-18DC-DA, PR-23DC-DA, PR-24DC-DA and PR-26DC- DA Series versions can accept analogue inputs. The type of signal connection can be set within the user program by selecting ether Analogue Input or Digital Input for that channel.

They will be recognized as analogue inputs when the input terminal is connected with an analogue function block, otherwise, they will be recognised as digital inputs Programmable Relay ● User Manual for ELC, EXM and PR Series 48 2020 v6.0 ● © Rievtech Co., Signal state AC Type DC Type OFF/0 Input Current ON/1 Input Current ON/1 > 79 VAC Typical 0.06 mA > 79 VAC > 10 VDC Input Current Typical 0.06 mA Typical 0.3 mA Analogue Input NOT APPLICABLE 0 to 10 VDC