Downloaded from https://www.everyspec.com MIL-STD-705C Unless otherwise specified in the procurment document, stabilization shall be considerd to have occurred when four consecu tive voltage and enerator (or exciter) field either remain current readings of the g unchanged or have only minor variations about an equilibrium condition with no evident continued increase or decrease in value after the last adjustment to the load, voltage or frequency has been made (see figure 619.2-II). Using the galvanometer matching networks, adjust the amplitudes of the voltage and current traces to minimums of 3 and 1.5 inches (approximately b. 75 and 40 millimeter) respectively.
On dc sets use an unenergized galvanometer for a zero voltage trace. Adjust the oscillograph chart speed such that individual waveform will be clearly visible. Adjust the oscillograph time marker to 0.01 seconds per line maximum or use a 60 Hz timing trace. After the stabilization has occurred record all instrument readings. With the oscillograph adjusted as in step b above, operate the oscillograph and reduce the load to zero in one step (do not use set circuit breaker to remove load). After allowing the voltage and frequency to return to steady state conditions after tie transient period, record all instrument readings.
Reapply the load in one step and allow the voltage and frequency to return to steady state conditions. Record all instrumen t readings. Repeat steps d and e above a sufficient number of times to obtain the oscillographic recordings of 3 voltage dips and 3 voltage rises. Repeat steps a thru f above for each additional voltage connection and c. d. e. f. g. frequency specified in the procurement document. Repeat steps a thru g above for any other load conditions specified in the procurement document. h. 619.2.4 Results. a.
From the oscillograms check to insure that the load reactance wa S not saturated and introducing excessive harmonics by determining that the ratios of the peak-to-peak voltage to the peak-to-peak current remain constant from the instant the load is first applied until steady-state renditions are reached. (For ac g enerators only - see figure 619.2-I). Using the no load to load oscillogram and the corresponding voltmeter b. readings, determine the voltage dip in percent using the following equation: Voltage Dip, in percent = where = Voltmeter reading at no load prior to applying load. = Rated voltage for which the generator is connected.
= Calculated voltage dip during the transient period where Method 619.2c 2