Department of Defense MIL-STD-705C — MIL-STD-705C Generator Sets Engine-Driven Test Methods Standard PDF

Downloaded from https://www.everyspec.com MIL-STD-705C b. Install appropriate pressure instrumentation to measure the following items: 1. Pressure in the vicinity of the combustion air intake (inside enclosed sets). 2. Exhaust gas pressure (combined exhaust gases in exhaust manifold or tailpipe). 3. Intake air manifold pressure (between air filters and manifold). obtain and maintain the ambient temperature within the chamber at the value specified in the procurement document.

During all parts of this method, the average of the eight ambient thermocouples (see MIL-HDBK-705, method 202.1) shall not be less than the specified temperature and of these eight thermocoup les, none shall indicate more than 5 F° (2.78 C°) above or below the specified ambient. d. Connect the load and field instrumentation in accordance with the c. Place the instrumented generator set in the temperature chamber and applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10, and as required for the test methods listed in 710.1.3.2 f below for a voltage connection and frequency specified in the procurement document. e.

Connect switch(es) to the g enerator armature coil(s), for which the temperature rise is to be determined, such that the coil(s) may be isolated for resistance measurements (if rapid access is available to isolate the individual windings this step may be omitted). 710.1.3.2 Test. a. Start and operate the generator set and allow the set to stabilize at rated load, rated voltage and rated frequency. During this period operate the recording meter(s) at a chart speed of not less than 6 inches per hour, and record all instrument readings including ambient temperature at minimum intervals of 10 minutes.

If necessary, adjustments to the load, voltage and frequency may be made to maintain rated load at rated voltage and frequency. Adjustments to the voltage and frequency shall be limited to those adjustments available to the operator, specifically adjustments to the voltage or frequency adjust devices. On sets utilizing a droop-type speed control system as the prime speed control, the speed and droop portions of the control may be adjusted. No other adjustments to the voltage and frequency control system shall be made unless permitted by the procurement document.

Adjustments to load, voltage or frequency controls shall be recorded on both the data sheet and the recording chart(s) at the time of adjustment. Unless otherwise specified in the procurement document, stabilization shall be considered to have occurred when four consecutive voltage and current recorded readings of the generator (or exciter) field either remain unchanged or have only minor variations about an equilibrium condition with no evident continued increase or decrease in value after the last adjustment to the load, voltage, or frequency has been made (see figure 710.1-I). Method 710.1d 2