Downloaded from https://www.everyspec.com MIL-STD-705C b. After stabilization has occurred stop the set so that temperatures of rotate components and windings may be taken. For application of the contact method to rotating parts, or the resistance method to the armature coils (see MIL-HDBK-705, methods 110.1 and 202.1); a quick shutdown of the set is mandatory. CAUTION: Do not connect bridges, meters or temperature measuring equipment for measuring resistance or temperature to circuits which may still be energizd, e.g., during the time that the set is coming to a stop. c.
Immediately after the shutdown, start to record the resistance bridge readings of the coils and the temperatures of the components where the contact method of measuring temperature rise is used. Readings of resistance measurements shall be recorded in accordance with instructions given in MIL-HDBK-705, method 110.1.
The first thermocouple reading shall be taken and recorded within 30 seconds after shutdown and additional readings taken and recorded at approximately 30 second intervals until one reading has been recorded after the temperature has begun to decrease, or three minutes has elapsed since set shutdown, whichever is longer, being certain that the maximum temperature reached by each component has been recorded. Continuous or multipoint temperature recorder(s) may be used to record component temperatures as long as the above time requirements are met. d. Repeat steps a thru c above for each of the coils specified in the procurement document. e.
Repeat steps a thru d above at each additional specified voltage connection and frequency and stabilization voltage. f. Unless otherwise specified, oprate the generator set in accordance with the instructions on the set or in the technical manual and perform the following methods at the specified ambient temperature, voltage connection and frequency: 1. Method 512.1, Circuit Interrupter Test (Short Circuit). 2. Method 512.3, Circuit Interrupter Test (Overvoltage and Undervoltage). 3. Method 513.2, Indicating Instrument Test (Electrical). 4. Method 655.1, DC Control Test. NOTE: The above methods are listed in numerical order; however, they need not be performed in this order. g.
Repeat paragraph a to establish stabilization values. Stabilization for the tests below will be considerd valid once the set has been operated a sufficient period of time to achieve the previously establish generator (or exciter) field voltage and current. The tests below shall be run sequentially with no shutdown between tests (if a shutdown occurs, for any reason, stabilization will have to be re-established): Method 710.1d 3