Downloaded from https://www.everyspec.com MIL-STD-705C 415.0.3.2.6 Armature I 2 R Loss. a. The armature I 2 R loss is defined as the product of the square of the armature current under any specified load and the resistance of the armature winding as measured in accordance with MIL-HDBK-705, method 105.1, corrected to 25 °C plus the stabilized temperature rise of the armature winding under the same load condition. The following formula for copper windings shall be used to determine the armature resistance: R c = R o (234.5 + T r ) 234.5 + T o Where: is the corrected resistance. is the measured resistance. is the temperature rise in Celsius degrees(C°).

is the temperature of the winding at the time R o is measured in degrees Celsius(°C). b. The armature I 2 R loss shall be calculated for rated load current in the armature winding(s) and used in this summation of losses. For a 3-phase machine the loss is the summation of the losses of the individual phase windings. c. To determine the stabilized armature winding temperature rise perform method 680.1, Temperature Rise Test ( Generator Only). 415.0.3.2.7 Field I 2 R loss. a.

The field I 2 R loss is defined as the product of the square of the field current under any specified load rendition and the resistance of the field as measured in accordance with MIL-HDBK-705, method 105.1, corrected to 25 °C plus the stabilized temperature rise of the field winding under the same load condition. Use the formula given in 415.0.3.2.6a above to determine the corrected field resistance. The field I b. 2 R loss shall be calculated for rated load field current in the field winding and used in the summation. To determine the Stabilized field winding temperature rise perform method 680.1, Temperature Rise Test ( Generator Only). c. Method 415.0b 4