Downloaded from https://www.everyspec.com MIL-STD-705C 415.0.3.2.8 Stray load loss. a. Short circuit the generator through the load current transformers (or shunt). A wye connected geenerator shall be shorted line-to-neutral (all phases) while a delta connected generator shall be shorted line-to-line (all phases). b. Start and operate the prime mover at rated generator speed. Adjust the external excitation supply for approximately 125 percent of rated current (If the phase currents of a mlti-phase machine are not approximately balanced, shut down the prime mover and the excitation supply and correct the trouble before proceeding). This test shall be performed with decreasing field current.

(During this test, should the field current accidentally be increased , it shall be returned to the value which will cause approximately 125 percent of rated generator current, then reduced to the desired value.) c. Decrease the excitation to obtain approximately 100, 75, 50, and 25 percent of rated current in the short-circuit ammeters. At each of these steps, including the 125 percent step, read and record the generator output current, the speed of the generator and the prime mover output power in kW (figure 415.0-VIII). d.

From the recorded values of prime mover output power subtract the bearing friction and windage loss, the brush friction loss, brush contact loss, and the armature I 2 R loss (which must be calculated for each current step- see 415.0.3.2.6), to obtain the stray load loss. e. Plot a curve of stray load loss versus armature current (figure 415.0-IV). f. The value of stray load loss at the armature current corresponding to rated armature current shall be used in the summation of losses. 415.0.3.2.9 Exciter loss. Connect a “dummy” load consisting of a resistor equal to the field resistance of the generator as defined in 415.0.3.2.7.

415.0.3.2.9.1 Rotating exciter directly coupled to the generator a. Start and operate the prime mover at rated generator speed, without generator excitation and with slip ring or commutator brushes raised. Adjust the exciter output voltage and current to the values required to excite the generator at rated load at rated voltage and rated speed. b. Read and record the prime mover output power in kW, and the output current and voltage of the exciter. c. From the prime mover output power subtracted the field I 2 R loss and the bearing friction and windage loss. This value is the exciter loss in kilowatts. 415.0.3.2.9.2 Rotating exciter separately driven. a.

Mechanically connect the exciter to a calibrated motor dynamotor (prime mover). Method 415.0b 5