Downloaded from https://www.everyspec.com MIL-STD-705C k. Measure the distance along the zero axis between the lines drawn from no. 2 and no. 4 peaks. Enter this distance on the work sheet. In the example, the distance was found to be 11.5 millimeters. Divide the measurement obtained in j by the measurement obtained in k to obtain the ratio between the two distances. In the example, this ratio is 0.61. On the graph, plot a point to the left of the no. 2 peak position, representing the ratio obtained in step 1 multiplied by the distance between 2 and 0 on the semi-log paper. In figure 425.1-V this distance is l. m. 6.1 squares to the left of the no. 2 peak position.
Draw a perpendicular line through this point and extending through “Curve B”. This line represents t = 0. Determine the reading at the point where “Curve B” intersects the t = 0 line. In the example, this reading is 18.5 millimeters. This value is substituted for in the following formula: n. X ' d = I R A T E D ( I t=0 + i ss ) I ss i s s is the distance perpendicular to the zero axis of the oscillogram between peaks at steady state. In the example, i ss =25 millimeters is the ammeter reading obtained from the data sheet. In the example, amperes. current of the generator phase under test. In the example, I RATED = 17.34 amperes. is the direct axis transient reactance.
In the example, X' d = 0.154 per unit or 15.4 percent. o. Repeat 425.1.3.3 for each oscillogram taken in 425.1.3.2. The value of the direct axis transient reactance shall be the average of the several computed values. Method 425.1b p. Compare the computed value of the direct axis transient reactance with the procurement document requirements. 425.1.5 Procurement d ocument requirements. The following item must be specified in the individual procurement document: a. Voltage connection(s) and frequency(ies) at which performed. Maximum allowable direct axis transient reactance expressed in per unit or percent. this method is to be b. (X' d ) at rated voltage Method 425.1b 3