MultiPlus 2kVA 230V 5. Configuration Settings may only be changed by a qualified engineer. Carefully read the instructions before changes are made. Batteries should be placed in a dry and well-ventilated area during charging. 5.1. Standard settings: ready for use On delivery, the MultiPlus is set to standard factory values. In general, these settings are suitable for single-unit operation. Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's documentation or to your battery supplier!
Standard MultiPlus factory settings Inverter frequency 50 Hz Input frequency range 45 - 65 Hz Input voltage range 180 - 265 VAC Inverter voltage 230 VAC Stand-alone / parallel / 3-phase stand-alone Search mode off Ground relay on Charger on/ off on Battery charge algorithm four-stage adaptive with BatterySafe mode Charge current 100% of the maximum charge current Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge) Automatic equalisation charging off Absorption voltage 14.4 / 28.8 / 57.6V Absorption time up to 8 hours (depending on bulk time) Float voltage 13.8 / 27.6 / 55.2V Storage voltage 13.2 / 26.4 / 52.8V (not adjustable) Repeated absorption time 1 hour Absorption repeat interval 7 days Bulk protection off AC input current limit 12A (= adjustable current limit for PowerControl and PowerAssist functions) UPS feature on Dynamic current limiter off WeakAC off BoostFactor 2 Programmable relay alarm function 5.2.
Explanation of settings Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software configuration programs (see Section 5.3). Inverter frequency Output frequency if no AC is present at the input. Adjustability: 50Hz; 60Hz Input frequency range Page 10 Configuration