Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 3.3. DC connection

MultiPlus-II inverter/charger Australia 3.3. DC connection To fully utilise the product's capacity, use batteries with adequate capacity and cables with sufficient cross-section. The DC cables must be copper and rated for 90єC. Refer to the below table. * Follow local installation rules. ** Do not locate battery cables in a closed conduit. “2x” means two positive and two negative cables. Remark: Internal resistance is an important factor when working with low-capacity batteries. Please consult your supplier or the relevant sections of our book ‘ Energy Unlimited ’, which is downloadable from our website. The AC and DC terminals are suitable for copper cables rated at 90°C.

Device voltage class of Battery Terminal: DVC B Connection Procedure Proceed as follows to connect the battery cables: Use a torque wrench with an insulated box spanner in order to avoid shorting the battery. Recommended torque: 12 Nm (M8 nut) Avoid shorting the battery cables. Undo the two screws at the bottom of the enclosure and remove the service panel. Connect the battery cables; see the appendix chapter for a connection overview. Tighten the nuts well for minimal contact resistance. The connector goes on first, then the flat washer, lock washer and nut. Tighten the nuts well for minimal contact resistance.

Page 8 Installation Model Recommended battery capacity (Ah) Recommended DC fuse current rating (A) Recommended cross section (AWG) per + and - connection terminal *, ** 0 – 5 m Recommended cross section (AWG) per + and - connection terminal *, ** 5 – 10 m 48/3000/35 100 - 400 125 35 mm² 70 mm² 48/5000/70 200 - 800 200 70 mm² 120 mm²