MultiPlus-II inverter/charger Australia 3.4. AC connection A residual current device is mandatory for all domestic and residential installations below a 32A rating: Use for a 3kVA inverter/charger a 30mA, 32A, type A RCD. Use for a 5kVA inverter/charger a 30mA, 50A, type A RCD. A fuse or automatic circuit breaker rated to support the expected load must be included in series with the output. And the cable cross-section must be sized accordingly. Both the earth leakage circuit breaker, automatic circuit breaker (or fuse) and cabling must be in accordance with the AS/NZS 3000 Electrical installations standard.
In case of an earth fault alarm, the inverter/charger shuts down, and error 8 is raised. For more information about error 8, see VE.Bus Error Codes . An earth fault can be recognised if the display shows: "Error 8." If the unit is not connected to the (optional) VRM portal via its GX device, install the product in a high-traffic area where an alarm would be noticed, or install an additional external earth fault alarm unit. This product is a safety class I product (supplied with a ground terminal for safety purposes). Its AC input and/or output terminals and/or grounding point on the outside of the product must be provided with an uninterruptible grounding point for safety purposes.
This product is provided with a ground relay (relay H, see appendix B) that automatically connects the Neutral output to the chassis if no external AC supply is available. If an external AC supply is provided, the ground relay H will open before the input safety relay closes. This ensures the correct operation of an earth leakage circuit breaker that is connected to the output. In a fixed installation, an uninterruptable grounding can be secured by means of the grounding wire of the AC input. Otherwise, the casing must be grounded. The AC and DC terminals are suitable for copper cables rated at 90°C. Device voltage class of AC Input Terminal:
DVC C Device voltage class of AC Out 1 and OUT 2 Terminal : DVC C For the location of the AC terminals, see the appendix. Recommended torque: 13mmІ treminal blocks: 1.6 Nm M6 bolts: 6 Nm Special notes regarding AS 4777.2 (Australia/New Zealand): 1. In installations where the continuity of the neutral to the load may not be interrupted, the installer must place a wire between AC-in N and AC-out N. Additionally, grid code “Australia X: AS/NZS 4777.2:2020+A1+A2 stand alone app. M (with N-bypass)” must be chosen. In this case the Earth relay (ground relay) remains open and in pass through mode the internal neutral relay will not operate.
In this configuration, the installation must incorporate a single permanent MEN connection at the Main Switchboard (MSB). This connection provides the required neutral-to-earth reference and ensures the correct operation of RCDs. Please see appendix for grid connected wiring diagram [30] . Please see appendix for stand alone wiring diagram [32] . Do not invert neutral and phase when connecting the AC. AC-in The AC input cable can be connected to the terminal block ‘AC–in’. From left to right:
“N” (neutral), “PE” (earth) and “L” (phase) The AC input must be protected by a fuse or magnetic circuit breaker rated at 32A (for the 3kVA model), and 50A (for the 5kVA model) or less, and the cable cross-section must be sized accordingly. If the input AC supply is rated at a lower value, the fuse or magnetic circuit breaker should be downsized accordingly. Generator connection requirements Page 9 Installation