MultiPlus-II inverter/charger Australia When a generator is connected to AC-in, an isolated (floating neutral) generator is the preferred arrangement. In this configuration the inverter’s internal ground relay is not used and remains open. The installation must have a single permanent MEN connection located at the Main Switchboard (MSB) . This MEN connection provides the required neutral-to-earth reference and ensures the correct operation of RCDs. Parallel MEN connections are not permitted . Neutral-earth bonded generators are not the preferred arrangement , because they may create parallel MEN paths where a MEN connection already exists at the MSB.
If a neutral-earth bonded generator is used, the bonding arrangement must be controlled by suitable switching or interlocking to ensure that only one effective MEN connection exists at any given time. Please see appendix for the generator connection diagram [31] . AC-out-1 The AC output cable can be connected directly to the terminal block ‘AC-out’. For a 3kVA unit with its PowerAssist feature enabled, the MultiPlus-II can add up to 3kVA to the output during periods of peak power requirement. Together with a maximum input current of 32A, this means that the output can supply up to 32 + 13 = 45A. From left to right:
“N” (neutral), “PE” (earth) and “L” (phase) For a 5kVA unit, the additional current is 22A, so the maximum output is 50 + 22 = 72A. An earth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load must be included in series with the output, and the cable cross-section must be sized accordingly. AC-out-2 A second output is available that disconnects its load in the event of battery operation. On these terminals, equipment that may only operate if AC voltage is available on AC-in-1, e.g., an electric boiler or an air conditioner, is connected. The load on AC-out-2 is disconnected immediately when the MultiPlus-II switches to battery operation.
After AC power becomes available on AC-in-1, the load on AC-out-2 will be reconnected with a delay of approximately 2 minutes. This allows a generator to stabilise. 3.5. Connection to the VRM Portal The connection of the product to the VRM portal requires an internet connection. This can be made via WiFi or a hardwired ethernet cable to an internet-connected router. The VRM site ID is located on a sticker inside the cable connections area of the device. For more information on how to set up the VRM portal, refer to the VRM Getting Started Manual . 3.6. Optional connections A number of optional connections are possible. For the location of the connection terminals, see the appendix chapter.
3.6.1. Remote control The product can be remotely controlled in two ways. With an external switch. Operates only if the switch on the MultiPlus-II is set to “on”. With a Digital Multi Control panel connected to one of the two RJ45 sockets. Operates only if the switch on the MultiPlus-II is set to “on”. 3.6.2. Programmable relay The product is equipped with a programmable relay. The relay can be programmed for all kinds of applications, such as an alarm relay or a starter relay for a generator. 3.6.3. Programmable analogue/digital input/output ports The product is equipped with two analogue/digital input/output ports. These ports can be used for several purposes.
One application is communication with the BMS of a lithium-ion battery. 3.6.4. Voltage sense To compensate for possible cable losses during charging, two sense wires can be connected with which the voltage directly on the battery or on the positive and negative distribution points can be measured. Use wire with a cross-section of 0.75mmІ (AWG 18). Page 10 Installation