Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 3.6.5. Temperature sensor

MultiPlus-II inverter/charger Australia During battery charging, the MultiPlus-II will compensate for the voltage drop over the DC cables up to a maximum of 1 Volt (i.e. 1V over the positive connection and 1V over the negative connection). If the voltage drop threatens to become larger than 1V, the charging current is limited in such a way that the voltage drop remains limited to 1V. 3.6.5. Temperature sensor For temperature-compensated charging, a temperature sensor can be connected. The sensor is isolated and must be fitted to the negative terminal of the battery. The temperature sensor is not supplied with 48V models. It can be ordered separately. Order number:

ASS000001000 Page 11 Installation