MultiPlus-II inverter/charger Australia 4. Configuration Read the instructions thoroughly before implementing changes. Settings may only be changed by a qualified electrical engineer. During charger configuration, the AC input must be removed. 4.1. Default settings On delivery, the MultiPlus-II is set to default values. In general, these settings are suitable for single-unit operation. Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's documentation or to your battery supplier!
Setting Default value Inverter frequency 50 Hz Input frequency range 45 – 65 Hz Input voltage range 187 - 250 VAC Inverter voltage 230 VAC Stand-alone / parallel / 3-phase stand-alone AES (Automatic Economy Switch) off Ground relay on Charger on/ off on Charging current 100% of the maximum charging current Battery charge curve four-stage adaptive with BatterySafe mode Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge) Automatic equalisation charging off Absorption voltage 57.6 V Absorption time up to 8 hours (depending on bulk time) Float voltage 55.2 V Storage voltage 52.8 V (not adjustable) Repeated absorption time 1 hour Absorption repeat interval 7 days Bulk protection on AC input current limit 32 A for 3kVA and 50 A for 5kVA (Is adjustable for PowerControl and PowerAssist functions) UPS feature on Dynamic current limiter off WeakAC off BoostFactor 2 Programmable relay alarm function PowerAssist on 4.2.
Configuring To configure the inverter/charger the following hardware is required: Interface MK3-USB - to convert VE.Bus to USB RJ45 UTP cable - to connect the inverter/charger to the interface. Page 12 Configuration