MultiPlus-II inverter/charger Australia Adjustability: 50 Hz; 60 Hz Adjustability: 210 – 245V Country / grid code standard For generator use, leave this setting at "None: feeding energy DC to grid not allowed". Accept wide input frequency range This setting is disabled when a grid code has been set. Input frequency range accepted by the MultiPlus-II. It synchronises within this range with the AC input frequency. The output frequency is then equal to the input frequency. Adjustability: 50, 60 or 45 – 65 Hz. Input voltage range This setting is disabled when a grid code has been set. Voltage range accepted by the MultiPlus-II. It synchronises within this range with the AC input.
The output voltage is then equal to the input voltage. Adjustability: Lower limit: 180 – 230 V Upper limit: 230 – 270 V The standard lower limit setting of 180V is intended for connection to a generator with unstable AC output. This setting may result in a system shut down when connected to a ‘brushless, self-excited, externally voltage regulated, synchronous AC generator’ (synchronous AVR generator). Most generators rated at 10kVA or more are synchronous AVR generators. The shutdown is initiated when the generator is stopped and revs down while the AVR simultaneously ‘tries’ to keep the output voltage of the generator at 230V.
The solution is to increase the lower limit setting to 220Vac (the output of AVR generators is generally very stable), or to disconnect the MultiPlu-II from the generator when a generator stop signal is given (with help of an AC contactor installed in series with the generator). Stand-alone/parallel operation / 2-phase / 3-phase setting Using several devices, it is possible to: Increase total inverter power (several devices in parallel) Create a split-phase system with a separate autotransformer: see the Victron Autotransformer product page . Create a 3-phase system. The standard product settings are for standalone operation.
For parallel, three-phase or split-phase operation, see the VE.Bus manual parallel and 3-phase systems . AES (Automatic Economy Switch) If this setting is turned ‘on’, the power consumption in no-load operation and with low loads is decreased by approximately 20%, by slightly 'narrowing' the sinusoidal voltage. Applicable in stand-alone configuration only. Instead of the AES mode, the search mode can also be chosen. If search mode is ‘on’, the power consumption in no-load operation is decreased by approximately 70%. In this mode the MultiPlus-II, when operating in inverter mode, is switched off in case of no load or very low load, and switches on every two seconds for a short period.
If the output current exceeds a set level, the inverter will continue to operate. If not, the inverter will shut down again. Search Mode The Search Mode ‘shut down’ and ‘remain on’ load levels can be set with VEConfigure. The standard settings are: Shut down: 40 Watt (linear load) Turn on: 100 Watt (linear load) Ground relay (see appendix B) With this relay, the neutral conductor of the AC output is grounded to the chassis when the back feed safety relays are open. Page 14 Configuration