Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 7.1. General error indications

MultiPlus-II inverter/charger Australia 7. Troubleshooting With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your Victron Energy supplier. Our recommendation is to use the Victron Toolkit app to find the description of all possible LED alarm codes. See here for download information: https://www.victronenergy.com/support-and-downloads/software#victron-toolkit-app . 7.1. General error indications Page 20 Troubleshooting Problem Cause Solution No output voltage on AC-out-2, even after waiting. in inverter mode AC input is not connecting. Follow steps in MultiPlus generator FAQ.

Unit will not switch over to generator or mains operation. Circuit breaker or fuse in the AC-in input is open as a result of overload. Remove overload or short circuit on AC-out-1 or AC-out-2, and reset fuse/breaker. Inverter operation not initiated when switched on. The battery voltage is excessively high or too low. No voltage on DC connection. Ensure that the battery voltage is within the correct range. 'Low battery' The battery voltage is low. Charge the battery or check the battery connections. 'Low battery' (Shutdown) The converter switches off because the battery voltage is too low. Charge the battery or check the battery connections.

Overload The converter load is higher than the nominal load. Reduce the load. 'Overload' (Shutdown) The converter is switched off due to excessively high load. Reduce the load. 'Over Temperature' The environmental temperature is high, or the load is too high. Install the converter in cool and well- ventilated environment, or reduce the load. 'Low Bat V Overload' (Shutdown) Low battery voltage and excessively high load. Charge the batteries, disconnect or reduce the load, or install higher capacity batteries. Fit shorter and/or thicker battery cables. 'High DC Ripple' Ripple voltage on the DC connection exceeds 1,5Vrms. Check the battery cables and battery connections.

Check whether battery capacity is sufficiently high, and increase this if necessary. 'DC Ripple Shutdown' The inverter is switched off due to an excessively high ripple voltage on the input. Install batteries with a larger capacity. Fit shorter and/or thicker battery cables, and reset the inverter (switch off, and then on again). The charger does not operate. The AC input voltage or frequency is not within the range set. Ensure that the AC input is between 185VAC and 265VAC, and that the frequency is within the range set (default setting 45-65 Hz). Circuit breaker or fuse in the AC-in input is open as a result of overload.

Remove overload or short circuit on AC-out-1 or AC-out-2, and reset fuse/breaker. The battery fuse has blown. Replace the battery fuse. The distortion or the AC input voltage is too large (generally generator supply). Turn the settings WeakAC and dynamic current limiter on. The charger does not operate. 'Bulk Protection' shown. is in 'Bulk protection' mode thus, the maximum bulk charging time of 10 hours is exceeded. Such a long charging time could indicate a system error (e.g. a battery cell short-circuit). Check your batteries. NOTE: You can reset the error mode by switching off and back on the . The standard factory setting of the 'Bulk protection' mode is switched on.

The 'Bulk protection' mode can be switched off with help of VEConfigure only. The battery is not completely charged. Charging current excessively high, causing premature absorption phase. Set the charging current to a level between 0.1 and 0.2 times the battery capacity.