MultiPlus-II inverter/charger Australia 7.2. VE.Bus error codes A VE.Bus system can display various error codes. These codes are displayed on the front GX display screen. To interpret a VE.Bus error code correctly, you should refer to the VE.Bus error codes documentation https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes . Page 21 Troubleshooting Poor battery connection. Check the battery connections. The absorption voltage has been set to an incorrect level (too low). Set the absorption voltage to the correct level. The float voltage has been set to an incorrect level (too low). Set the float voltage to the correct level.
The available charging time is too short to fully charge the battery. Select a longer charging time or higher charging current. The absorption time is too short. For adaptive charging this can be caused by an extremely high charging current with respect to battery capacity, so that bulk time is insufficient. Reduce the charging current or select the 'fixed' charging characteristics. The battery is overcharged. The absorption voltage is set to an incorrect level (too high). Set the absorption voltage to the correct level. The float voltage is set to an incorrect level (too high). Set the float voltage to the correct level. Poor battery condition. Replace the battery.
The battery temperature is too high (due to poor ventilation, excessively high environmental temperature, or excessively high charging current). Improve ventilation, install batteries in a cooler environment, reduce the charging current, and connect the temperature sensor. The charging current drops to 0 as soon as the absorption phase initiates. Defective battery temperature sensor Disconnect the temperature sensor plug in the . If charging functions correctly after approximately 1 minute, the temperature sensor should be replaced.
The battery is over-heated (+50°C) Install the battery in a cooler environment Reduce the charging current Check whether one of the battery cells has an internal short circuit Code Meaning: Cause/solution: 1 Device is switched off because one of the other phases in the system has switched off. Check the failing phase. 3 Not all, or more than, the expected devices were found in the system. The system is not properly configured. Reconfigure the system. If the error persists, possible communication cable error. Check the cables and switch all equipment off, and then on again. 4 No other device whatsoever detected. Check the failing unit. Check the communication cables. 5 Overvoltage on AC-out.
Check the AC cables. 10 System time synchronisation problem occurred. Should not occur in correctly installed equipment. Check the communication cables. 14 Device cannot transmit data. Check the communication cables (there may be a short circuit). 17 One of the devices has assumed 'master' status because the original master failed. Check the failing unit. Check the communication cables. 18 Overvoltage has occurred. Check AC cables. 22 This device cannot function as 'slave'. This device is an obsolete and unsuitable model. It should be replaced.