Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 7.2. VE.Bus error codes

MultiPlus-II inverter/charger Australia Page 22 Troubleshooting Code Meaning: Cause/solution: 24 Switch-over system protection initiated. Should not occur in correctly installed equipment. Switch all equipment off, and then on again. If the problem recurs, check the installation. Possible solution: increase lower limit of AC input voltage to 210 VAC (factory setting is 180 VAC) 25 Firmware incompatibility. The firmware of one the connected devices is not sufficiently up to date to operate in conjunction with this device. 1) Switch all equipment off. 2) Switch the device returning this error message on. 3) Switch on all other devices one by one until the error message reoccurs.

4) Update the firmware in the last device that was switched on. 26 Internal error. Should not occur. Switch all equipment off, and then on again. Contact Victron Energy if the problem persists.