Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 11.1. Connection Overview

MultiPlus-II inverter/charger Australia 11. Appendix 11.1. Connection Overview Page 28 Appendix Reference Description Connection A Load connection. AC-OUT-1 Left to right: N (neutral), PE (earth/ground), L (phase) B Load connection. AC-OUT-2 Left to right: N (neutral), PE (earth/ground), L (phase) C AC input. AC-IN Left to right: N (neutral), PE (earth/ground), L (phase) D Programmable (AUX) relay; left to right NO, NC, COM. E To start without Assistants Press and hold this button when starting F Primary ground connection M6 (PE) G Battery positive connection. M8 H Battery minus connection. M8 I Switch -:On, 0:Off, =:charger only J Terminals top to bottom: 1.

Auxiliary power supply 12 V 100 mA 2. Programmable open collector ooutput (K1) 70V 100mA 3. External ground relay + 4. External ground relay – 5. Analog/digital (AUX) input 1 + 6. Analog/digital (AUX) input 1 – 7. Analog/digital (AUX) input 2 + 8. Analog/digital (AUX) input 2 – 9. Temperature sense + 10 .Temperature sense –