Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 10.1. Technical specifications

MultiPlus-II inverter/charger Australia Page 27 Technical specifications MultiPlus-II GX 230V 48/3000/35-32 48/5000/70-50 VE.Bus communication port Yes VE.Can port Yes VE.Direct port Yes USB port Yes Ethernet port Yes WiFi Yes General purpose communication port Yes, 2x Remote on/off terminal Yes Operating temperature range -20 to +65°C (fan-assisted cooling) Rated short-time withstand current (Icw) 6kA Humidity (non-condensing) max 95% Environmental category Indoor conditional Pollution degree 2 Maximum altitude 2000m Country of manufacture China India ENCLOSURE Material and colour Steel, blue RAL 5012 Protection category IP21 Battery connection M8 bolts AC connection Screw terminals for wire up to 13mm² (6 AWG) Weight 18 kg 29 kg Dimensions hxwxd (mm) 506 x 275 x 147 565 x 320 x 148 STANDARDS Safety EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2 Emission, Immunity EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3 1) Can be adjusted to 60Hz 3) Non-linear load, crest factor 3:1 2) Protection key:

4) Up to 25°C ambient a) output short circuit 5) Other chemistries are possible as well, providing the charger is configured confirm the battery manufacturer’s b) overload specifications. c) battery voltage too high 6) Programmable relay which can be set for general d) battery voltage too low alarm, DC under voltage or genset start/stop function. AC e) temperature too high rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC f) 230Vac on inverter output g) input voltage ripple too high