omron — 2-1-3 Connecting the Power Supply

2 Installing the NB Unit and Connecting Peripheral Devices 2-1-3 Connecting the Power Supply 2-1 Installing the NB Unit • Do not connect an AC power supply to the DC power terminals. • Use a DC power with a slight voltage fluctuation and reinforced or double insulation, and that will provide a stable output even if the input is momentarily interrupted for 10 ms. Rated Power Supply Voltage: DC 24 V (Allowable range DC 20.4 ~ 27.6 V)  Power Supply The connectable power supply specifications are as follows: figure out a suitable power supply specification so as to satisfy the requirement for power supply capacity.

2-1-3 Connecting the Power Supply  NB5Q/NB7W/NB10W-TW  B The reverse side of NB 0V 24V MCCB DC24V  NB3Q -TW  B The reverse side of NB 24V 0V MCCB DC24V • Before connecting the power supply to the NB unit, mount the cable on the terminal block. Make the connection by using terminal screws crimping on a twisted-pair cable with a crimping range of 12~26 AWG, and only 6.5 mm of insulation peel of the cable needs to be peeled off. Tighten the terminal screws at a torque of between 0.3 and 0.5 N·m. Make sure the screws are properly tightened. Only NB3Q-TW  B has a different pin arrangement of the terminal block. Do not make use of the terminal block of NB3Q-TW  B for other equipments.

NB-series Programmable Terminals Setup Manual(V107) 2-5 Precautions for Safe Use 2 Models Rated Voltage Allowable Voltage Range Power NB3Q-TW00B DC24V DC20.4V to 27.6V 5W NB3Q-TW01B 9W NB5Q-TW00B 6W NB5Q-TW01B 10W NB7W-TW00B 7W NB7W-TW01B 11W NB10W-TW01B 14W Precautions for Safe Use