2 Installing the NB Unit and Connecting Peripheral Devices 2-4 Serial Communication Connection 2-4 Serial Communication Connection 2-4-1 Host Link Connection Method Host Link is a connection method in which one PLC is connected to one NB Unit. There are 2 kinds of connection methods: RS-232C and RS-422A. The RS-232C connection method using serial ports COM1/COM2 This is the simplest and most feasible method. NB Unit Host 2-4-1 Host Link Connection Method RS-232C cable (maximum length: 15m) The following cables are recommended. XW2Z-200T (Cable length: 2m) by OMRON XW2Z-500T (Cable length:
5m) by OMRON The RS-422A connection method using the serial port COM2 With this method, the communication distance can be extended to a maximum of 500m. NB Unit Host RS-422A cable (maximum length: 500m) The following cables are recommended. NB-RSEXT-2M (Cable length: 2m) by OMRON Note please adopt 4-wire RS-422A connection, and Host Link does not support 2-wire RS-485 connection. Connectable Units at the host side When using OMRON PLCs, the Units with built-in Host Link function vary depending on models and series. There is also the CPU Unit connected in a Host Link method through adding the serial communication unit or communication option board.
When connecting, confirm the connected PLC’s series, model and the models of the installed circuit board/Unit. As to the Units at the host side which can be connected to NB series Unit by RS-232C or RS-422A through a Host Link, refer to A-5 List of Models in the NB Series Setup Manual . NB-series Programmable Terminals Setup Manual(V107) 2-11 2