2 Installing the NB Unit and Connecting Peripheral Devices When connecting to CS-Series CPU Units For CS1G/H-CPU (-V1) types and CS1G/H-CPU H types Connection Methods Connect to the RS-232C port built in the CPU Unit or the RS-232C port of the communication board. When connecting to the peripheral port, a connection cable dedicated for the peripheral port is needed (CS1W-CN118 type). Only RS-232C can be used for connection. PLC System Settings Area When connecting to CS-Series CPU Unit, refer to the following table and set the communication conditions as follows in [PLC System Settings] based on the communication port in use.
*1 The communication speed should be set to the same value as that of the NB Unit. [PLC System Settings] can be directly set with a peripheral tool (programming console), or it can be set by transmitting the [PLC System Settings] set up by a peripheral tool (CX-Programmer) to the CPU Unit. For details about the [PLC System Settings], refer to SYSMAC CS Series Operation Manual (W339). Settings for the front-side Switches Set the DIP switches 4 or 5 as follows according to the NB-Series’ port connected. DIP Switch (in the battery jar) • When connecting a NB-Series Unit to a peripheral port, set SW4 to [ON] (communications carried out according to the PLC system settings).
• When connecting a NB-Series Unit to a RS-232C port, set SW5 to [OFF] (communications carried out according to the PLC system settings). Peripheral Port Mainly used for connecting peripheral tools, ect. (also used for connecting RS-232C devices) RS-232C Port Mainly used for connecting RS-232C devices (also used for connecting CX-Programmer) 2-18 NB-series Programmable Terminals Setup Manual(V107) Connection Methods Channel No. Write Value Setting Use the RS-232C port built in CS1G/H, CS1G/H-H 160 8000 Use Host Link 161 0000~000A(*1) Communication speed 163 0000 Unit No.
00 Use the peripheral port of CS1G/H, CS1G/H-H 144 8000 Use Host Link 145 0000~000A(*1) Communication speed 147 0000 Unit No. 00