omron — 2-4-3 Settings for each Unit

2 Installing the NB Unit and Connecting Peripheral Devices 2-4 Serial Communication Connection When connecting to CJ Series CPU Units For CJ1G-CPU  type, CJ1G/H-CPU  H types and CJ1M-CPU  type  Connection Methods Connect to the RS-232C port built in the CPU Unit or the RS-232C port of the communication board. When connecting to the peripheral port, a connection cable dedicated for the peripheral port is needed (CS1W-CN118 type). Only RS-232C can be used for connection.

 PLC System Settings Area (for RS-232C) When connecting to the CJ-Series CPU Unit, refer to the following table and set the communication conditions as follows in [PLC System Settings] based on the communication port in use. 2-4-3 Settings for each Unit *1 The communication speed should be set to the same value as that of the NB Unit. [PLC System Settings] can be directly set with a peripheral tool (Programming console), or it can be set by transmitting the [PLC System Settings] set up by a peripheral tool (CX-Programmer) to the CPU Unit. For details about the [PLC System Settings], refer to SYSMAC CJ Series Operation Manual (W393).

 Settings for the front-side Switches Set the DIP switches 4 or 5 as follows according to the NB-Series’ port connected. DIP Switch(in the battery jar) • When connecting a NB-Series Unit to a peripheral port, set SW4 to [ON] (communications carried out according to the PLC system settings). • When connecting a NB-Series Unit to a RS-232C port, set SW5 to [OFF] (communications carried out according to the PLC system settings). Peripheral Port Used for connecting programming consoles, ect. RS-232C Port Used for connecting devices other than programming consoles. NB-series Programmable Terminals Setup Manual(V107) 2-19 2 Connection Methods Channel No.

Write Value Setting Use the RS-232C port built in CJ1G-CPU type, CJ1G/H-CPUH types, CJ1M-CPU types 160 8000 Use Host Link 161 0000~000A(*1) Communication speed 163 0000 Unit No. 00 Use the peripheral port of CJ1G-CPU type, CJ1G/H-CPUH types, CJ1M-CPU type 144 8000 Use Host Link 145 0000~000A(*1) Communication speed 147 0000 Unit No. 00