2 Installing the NB Unit and Connecting Peripheral Devices When connecting to CJ2-Series CPU Units For CJ2M-CPU3 type, CJ2M-CPU1 type and CJ2H-CPU6 (-EIP) type Connection Methods Connect to the RS-232C port built in the CPU Unit or the RS-232C port of the communication board. PLC System Settings Area (for RS-232C) Carry out setting by transmitting the [PLC System Settings] set up by a peripheral tool (CX- Programmer) to the CPU Unit. On the [Serial Port] options page of [PLC System Settings], set the connection mode to Host Link: 7 Data Bits, 2 Stop Bits, Even. And set the communication speed to the same as that of the NB Unit.
For details about the [PLC System Settings], refer to SYSMAC CJ2 Series Software User ’ s Manual (W473). Settings for the front-side Switches Set the DIP switch 5 of the CPU Unit as follows according to the NB-Series’ port connected. Turn DIP SW5 OFF for serial communications. 2-20 NB-series Programmable Terminals Setup Manual(V107)