omron — 2-4-3 Settings for each Unit

2 Installing the NB Unit and Connecting Peripheral Devices 2-4 Serial Communication Connection When connecting to a CS-Series Serial Communication Board For CS1W-SCB21 type (Both of port 1 and 2 are RS-232C ports) For CS1W-SCB41 type (Port 1 is RS-232C port and Port 2 is RS-422A/485 port.)  Settings for the DM Fixed Allocation Area of the CPU Unit Write settings directly to the [DM Fixed Allocation Area] of the CPU Unit (System Settings Area) with a peripheral tool (programming console or CX-Programmer).

After finishing the write-in, the settings can be activated through any of the methods of reconnecting the power supply, restarting the Unit, reactivating the communication port, executing the STUP instruction. The followings are the Channel Nos. and settings of the DM Fixed Allocation Area. It is the same when using RS-232C, RS-422A (port 2 of the CS1W-SCB41 type). 2-4-3 Settings for each Unit *1 The communication speed should be set to the same value as that of the NB Unit.  Settings for front-side switches (For RS-422A) Port1 RS-232C Terminating resistance switch Set to ON (right position). Port2 RS-422A/485 Two-wire/four-wire switch RS-422A: [4] (four-wire)(right position) RS-485: