Appendices . A-4-4 Method for Fabricating the Cable for Connection to OMRON PLC When fabricating the cable for connecting the NB Unit and OMRON PLC, refer to the following methods: These examples assume the CJ1W-SCU OMRON PLC. For the pin numbers, check the specification of the actual target device before connection.
A-4 Fabrication of the Connection Cable A-4-4 Method for Fabricating the Cable for Connection to OMRON PLC COM1 The cable for connecting the NB3Q Unit serial port COM1 to OMRON PLC (RS-232C) COM1 (female) at the NB Unit side NB Unit side Shielded Cable OMRON PLC side RS232 port at the OMRON PLC side (female) 1 6 1 6 5 9 5 9 The cable for connecting the NB3Q Unit serial port COM1 to OMRON PLC (RS-422A) COM1 (female) at the NB Unit side NB Unit side OMRON PLC side 1 6 Shielded Cable 5 9 Note If the RS-485 connection is adopted, all needed to do is to connect the No.6 and No.8 pins and the shielded cable to the corresponding pins on the PLC side.
Note For NB3Q, terminating resistance is shortened by the DIP switch. Refer to "1-2 Part Specifications" for more details. NB-series Programmable Terminals Setup Manual(V107) A-11 Signal Name Pin No. FG Connector Hood SDB+ 1 SD(TXD) 2 RD(RXD) 3 RS(RTS) 4 CS(CTS) 5 RDB+ 6 SDA- 7 RDA- 8 SG 9 Pin No. Signal Name Connector Hood FG 2 SD 3 RD 4 RS 5 CS 6 5V 7 NC 8 NC 9 SG App Signal Name Pin No. SDB+ 1 SD(TXD) 2 RD(RXD) 3 RS(RTS) 4 CS(CTS) 5 RDB+ 6 SDA- 7 RDA- 8 SG 9 FG Connector Hood Pin No. Signal Name 1 RDA- 2 RDB+ 3 SDA- 4 SDB+ 5 FG