Victron Nucleo GX — 12.3.1. DVCC effects when there is more than one Multi/Quattro connected

Nucleo GX Manual 12.3.1. DVCC effects when there is more than one Multi/Quattro connected When DVCC is enabled, the Multi/Quattro system connected to the built-in VE.Bus port (single unit, or multiple units configured for parallel, split-phase or three-phase operation) is controlled by DVCC. A secondary Multi/Quattro connected to the GX device via an MK3-USB interface is not controlled by DVCC by default and operates according to its own internal configuration. DVCC - Distributed Voltage and Current Control Page 109 The Charge Control menu (Settings → System Setup → Charge Control) includes the option ‘Managed battery controls all Multis and Quattros’.

This option is only displayed when an additional Multi/Quattro is connected to the GX device via an MK3-USB interface. When enabled (disabled by default), secondary Multi/ Quattro devices connected via MK3-USB are also controlled by the managed (CAN-bus) battery. In this case, the Charge Voltage Limit (CVL), Discharge Current Limit (DCL) and Charge Current Limit (CCL) provided by the BMS are duplicated to all connected Multis and Quattros. This ensures that all units use the same charge voltage, and that all units stop discharging if the battery requests discharge to stop. Limited CCL control The CCL is not distributed or shared between multiple inverter/chargers.

Instead, the full CCL value is applied to each controlled unit. This behaviour is intended for systems where, for example, a genset is connected to the secondary Multi/Quattro. It is the responsibility of the installer to ensure that the CCL is not exceeded if multiple Multis/Quattros are charging at the same time.