Nucleo GX Manual 12.4. DVCC features for all systems The following features apply to all system types when DVCC is enabled, regardless of whether: The ESS Assistant is used or not The system uses lead-acid or other standard batteries An intelligent CAN-bus BMS battery is installed These features are active in all configurations where DVCC is enabled. 12.4.1. Limit charge current Particulars: 1. If a CAN-bus BMS is connected and the BMS requests a maximum charge current that is different from the user-configurable setting, the lower of the two will be used. 2. This mechanism only works for Victron inverter/chargers including Inverter RS, Multi RS, Solar chargers incl.
MPPT RS and Orion XS DC-DC battery chargers. Other chargers, such as Skylla-i’s are not controlled and also their charge current is not taken into account. The same applies for devices that are not connected to the GX device, such as an alternator. Worded differently: the total charge current of the inverter/chargers and all MPPT solar chargers will be controlled, nothing else. Any other sources will be extra charge current, unaccounted for. Even when installing a BMV or other battery monitor. 3. DC Loads may not be accounted for, unless a SmartShunt or BMV-712 is installed and correctly configured as a DC meter .
For example, without the DC load monitor a configured maximum charge current of 50A and DC Loads drawing 20A, the battery will be charged with 30A, not with the full allowed 50A. With the SmartShunt configured as a DC meter, maximum charge current configured at 50A and DC system shunt reports a draw of 25A, then the chargers are set to charge with 50 + 25 = 75A. If you have one or more shunts configured for "DC system" (when more than one, they are added together), then the DVCC charge current limit compensates for both loads and chargers. It will add extra charge current if there is a load, and subtract it if there is another charger in the DC system.
DC "loads" and "sources" are not compensated for in either direction. 4. Current drawn from the system by the inverter/charger is compensated for. For example, if 10A is drawn to power AC loads and the limit is set to 50A, the system will allow the MPPT solar chargers to charge with a maximum of 60A. 5. In all situations, the maximum charge limit configured in a device itself, i. e. the Charge current limit set with VictronConnect or VEConfigure for Orion XS DC-DC battery chargers, MPPT solar chargers or inverter/chargers will still be in effect. An example to illustrate this:
in case there is only an inverter/charger in the system and in VEConfigure or VictronConnect the charge current is configured to 50A. And on the GX device, a limit of 100A is configured, then the working limit will be 50A. 6. DVCC charge current limits are not applied to DC MPPTs when ESS is enabled with Allow DC MPPT to export. This is to get maximum output from the solar panels for export. 12.4.2. Limit managed battery charge voltage DVCC - Distributed Voltage and Current Control Page 110 Limit charge current is a user-configurable setting that defines the maximum total charge current allowed in the system. It is available under: Settings → System Setup → Charge Control on the GX device.
In systems with DVCC enabled, charge sources are prioritised as follows: 1. MPPT Solar Chargers (including MPPT RS) 2. Orion XS DC-DC Battery Chargers 3. Inverter/Chargers (including Inverter RS and Multi RS) Some managed batteries, such as BYD and Pylontech, may require a reduced charge voltage during their initial commissioning period. This helps ensure proper cell balancing in the first few weeks of operation. The Limit managed battery charge voltage feature is designed specifically for this purpose. When enabled, it allows to temporarily reduce the maximum charge voltage, even if the battery’s BMS normally permits a higher voltage.