Nucleo GX Manual 18. Troubleshooting 18.1. Error Codes Different origins of errors The GX device can display its own error codes, as well as those from connected devices.For device-specific codes, refer to: Multi and Quattro inverter/chargers: VE.Bus Error Codes MPPT Solar Chargers: MPPT Solar Charger Error Codes GX Error #42 - Storage corrupt The internal flash memory is corrupt. This partition stores settings, serial numbers, and Wi-Fi credentials. Solution: The device must be returned for repair or replacement. This cannot be fixed via firmware or in the field. GX Error #46 - Data partition full The alarm triggers when free space on the data partition drops below 10%.
A full data partition can cause Venus OS to malfunction and prevent services from starting. The most common cause is data written by third-party apps such as Node-RED or Signal K. To see which apps are installed, go to Settings → General → Support status. For solutions, see Venus OS Large - Disk space issues / data partition full GX Error #47 - Data partition issue The internal storage is likely damaged, causing the device to lose configuration. Solution: Contact your dealer or installer. See our Victron Energy Support page. GX Error #48 - DVCC with incompatible firmware DVCC is enabled, but not all system components are running compatible firmware. Solution:
Refer to the DVCC chapter of this manual for firmware requirements. Note for systems with Pylontech and BMZ batteries: Since Venus OS v2.80, DVCC is enforced for Pylontech and BMZ batteries. Older systems may show this error. Solution: Disable automatic updates; Settings → General → Firmware → Online updates → Auto update. Roll back to v2.73 (see Install a specific firmware version from SD/USB ). And after that, consider having an installer update all device firmware. Note for systems with BYD, MG Energy Systems and Victron Lynx Ion BMS batteries: Since Venus OS v2.40, DVCC auto-enables for supported BMS types. Older systems may lack components to support this. Solution:
Disable automatic updates; Settings → General → Firmware → Online updates → Auto update. Roll back to v2.33; to roll back to a previous firmware version see Install a specific firmware version from SD/USB . Ensure DVCC is disabled. Consult your installer to check if your system uses two-wire control (earlier alternative to DVCC). If there are no charge/discharge wires between BMS, inverter/chargers, and charge controllers, DVCC is required for the above-mentioned battery brands. This also requires minimum firmware versions on connected devices. GX Error #49 - Grid meter not found In ESS setups with External Grid Meter selected, no meter was detected. Solution:
Check system wiring and configuration. GX Error #51 - mk3 firmware needs update Update the MK3 controller inside the GX device to enable recent features like generator start/stop warm-up/cooldown. To update: Page 159 Troubleshooting