Victron Nucleo GX — 18.2.24. Q25: My GX device reboots itself. What is causing this behavior?

Nucleo GX Manual Consideration when removing pin 7 Removing pin 7 disables the ability of the GX device to fully switch off the VE.Bus device. The unit will stop charging and inverting, but will remain in standby, drawing more power than if pin 7 were intact. This is primarily relevant in marine and automotive systems, where devices are routinely switched off. In such cases, do not remove pin 7 , and instead power the GX device from the battery directly. 18.2.21. Q21: I love Linux, programming, Victron and the NGX. Can I do more? Yes you can! We intend to release almost all code as open source, but we are not that far yet.

What we can offer today is that many parts of the software are in script or other non-precompiled languages, such as Python and QML, and therefore available on your Nucleo GX and easy to change. Root password and more information is available here . Please check the remote switch connection on the Multi control PCB. There should be a wire bridge between the left and middle terminal. The NGX switches a line which enables the power of the Multi control board. After 10 seconds this line is released and the Multi should take over from there. When the remote switch connection is not wired, the Multi is unable to take over it's own supply.

The NGX will retry, the Multi will boot and after 10 seconds stop, and so on. 18.2.22. Q23: Multi restarts all the time (after every 10sec) 18.2.23. Q24: What is Error #42? Error #42 – Hardware fault indicates corrupt flash storage on the GX device. This prevents settings from being saved. After a reboot, all settings revert to defaults, and may lead to further issues. This fault is not field-repairable and cannot be fixed by service departments. Please contact your dealer to arrange a replacement. Note: Firmware versions prior to v2.30 did not report this error. Since v2.30, Error #42 is visible both on the device GUI and in the VRM Portal.

There are several reasons why a GX device may reboot itself. 18.2.24. Q25: My GX device reboots itself. What is causing this behavior? One of the most common causes is loss of communication with the VRM online portal. However, this is only true if the "Reboot device when no contact" option (disabled by default) has been enabled in the VRM online portal settings. If there is no contact with the VRM portal for the time period set in 'No contact reset delay', the GX device will automatically reboot. This process is repeated until communication with the VRM portal is restored. See also chapter Datalogging to VRM - Network watchdog: auto-reboot. 1.

Check the network connection between your GX device and the router. See Troubleshooting data logging . 2. Preferably use an ethernet connection between your GX device and the router. 3. Tethered or hotspot connections, e.g. with a cell phone, are not reliable and are often interrupted or do not automatically restore the connection once it has been lost. Therefore, this is not recommended. Other common reasons that cause the GX device to automatically restart are: System overload (either CPU, memory, or both). Page 164 Troubleshooting