Victron Energy Nucleo GX — 20.3. Modbus holding registers for the ComAp InteliLite 4 controller

Nucleo GX Manual 20.3. Modbus holding registers for the ComAp InteliLite 4 controller The following table lists the required ComAp Modbus configuration. In addition to the listed holding registers, Coil 4700 is used to start and stop the genset. Table 1. Holding registers Page 181 Appendix Register(s) Com. Obj.

Name DIM Type Dec Group 01004 10123 RPM rpm int16 0 Engine 01006 9152 T-Coolant °C int16 0 Controller I/O 01008 9151 P-Oil bar int16 1 Controller I/O 01013 - 01014 8206 Running Hours h int32 1 Statistics 01020 8202 Load P kW int16 0 Load 01021 8524 Load P L1 kW int16 0 Load 01022 8525 Load P L2 kW int16 0 Load 01023 8526 Load P L3 kW int16 0 Load 01036 8210 Generator Frequency Hz uint16 1 Generator 01037 8192 Generator Voltage L1-N V uint16 0 Generator 01038 8193 Generator Voltage L2-N V uint16 0 Generator 01039 8194 Generator Voltage L3-N V uint16 0 Generator 01043 8198 Load Current L1 A uint16 0 Load 01044 8199 Load Current L2 A uint16 0 Load 01045 8200 Load Current L3 A uint16 0 Load 01053 8213 Battery Volts V int16 1 Controller I/O 01055 9153 Fuel Level % int16 0 Controller I/O 01263 - 01264 8205 Genset kWh kWh int32 0 Statistics 01298 9244 Engine State String list Info 01301 12944 Connection Type ID String FW Version Controller Mode Gen-Set Name String list Info 01307 - 01322 24501 Long string Info 01323 - 01330 24339 Short string Info 01382 9887 string list Info 03000 - 03007 8637 Short string Basic Settings / Name