Victron Energy Nucleo GX — 20.4. Modbus holding registers for supported DSE genset controllers

Nucleo GX Manual 20.4. Modbus holding registers for supported DSE genset controllers The following table lists the Modbus holding registers the GX device reads. Note that this Modbus table reflects the DSE register list, not the GX device's. These definitions follow the Deep Sea Electronics GenComm standard (Version 2.236 MF). The Modbus register list for reading this data from the GX device can be found in the download section on the Victron website. The registers marked required in the Remarks column are critical for identifying the DSE genset controllers in the GX device and for proper operation of the Victron ecosystem with the generator. Don't change them.

All other registers are optional. Note: Page and Register offset are terminology from the DSE GenComm standard. Table 2.

Holding registers Page 182 Appendix Register(s) Page Offset Name Units Remarks 768 3 0 Manufacturer code Required for DSE controller 769 3 1 Model number identification 770 3 2 Serial number 772 3 4 Control mode 1024 4 0 Oil pressure kPa 1025 4 1 Coolant temperature °C 1026 4 2 Oil temperature °C 1027 4 3 Fuel level % 1029 4 5 Engine battery voltage V 1030 4 6 Engine speed RPM 1031 4 7 Generator frequency Hz Required for the Victron ecosystem to work properly 1032 4 8 Generator L1-N voltage V 1034 4 10 Generator L2-N voltage V 1036 4 12 Generator L3-N voltage V 1044 4 20 Generator L1 current A 1046 4 22 Generator L2 current A 1048 4 24 Generator L3 current A 1052 4 28 Generator L1 watts W 1054 4 30 Generator L2 watts W 1056 4 32 Generator L3 watts W 1536 6 0 Generator total watts W 1558 6 22 Generator % of full power % 1798 7 6 Engine run time Seconds 1800 7 8 Generator pos.

kW hours kWh 1808 7 16 Number of starts From 2048 8 Alarm conditions 4096 to 4103 16 Control registers From 39424 154 Alarm conditions