beckhoff TwinCAT 2 — 6.5 Axis parameters, axis monitoring and axis calibration

Axis commissioning When the calibration travel of an axis is started, it begins with the velocity reference travel in a positive direction (the global tab for the axis) mentioned above. The actual direction is specified by the encoder's incremental tab. The axis stops when the signal bit for the calibration cam is set in its NC-PLC interface. This cam allows a specific pulse to be selected on rotating encoder systems with one synchronizing pulse per rotation. The axis now starts again to leave the cam. It now executes the velocity reference travel in the negative direction (global tab for the axis) until the signal bit is cleared.

Without changing its velocity, the axis now continues until the encoder's synchronous latch has asserted. Only now does the axis stop. The distance covered between the assertion of the latch and the location at which the axis of comes to a halt is determined. The total formed by adding this distance to the reference position (incremental tab of the in encoder) is set as the new actual axis position. This procedure allows the synchronous pulse from a selected rotation of the axis to be assigned to an absolute position in the machine. The calibration is started by means of under Axis Online in the System Manager . Numerical Control (NC) Basics 66 Version: 1.2