Orion-Tr Tr Smart DC-DC Charger Non-Isolated — 7.5. Full rated output not reached

Orion-Tr Smart DC-DC Charger Non-Isolated To check if the battery has been misused: 1. Check if the battery has been totally discharged at all. Total and very deep discharge will damage a battery. Check the battery monitor setting history on the VRM portal. Look for the deepest discharge, the lowest battery voltage, and the number of full discharges. 2. Check if the battery has been charged with too high voltage. Very high charge voltage will damage the battery. Check the maximum battery voltage and the high voltage alarms in the battery monitor. Check if the measured maximum voltage has exceeded the battery manufacturer's recommendations. 7.5.

Full rated output not reached There are a few reasons why the is not reaching its full rated output. Alternator rating (during idling) too small If the alternator power rating is less than the nominal power rating, it cannot output more power than the connected alternator can provide. To determine whether the alternator is the limiting factor, see Insufficient alternator power [20] . Temperature protection active When the heats up, eventually the output current will derate. When the current is reduced, naturally the output power will reduce as well.

The is operational up to an ambient temperature of 55°C, with full rated output up to 40°C when mounted on a vertical surface with the terminals facing downwards and sufficient free space for ventilation. Above 40°C, the output current derates by 3% per °C. If the is located in a closed enclosure, such as a cabinet, make sure that cold air can enter and hot air can leave the enclosure. Mount vents in the enclosure. For very hot environments consider mechanical air extraction or provide air conditioning. Page 22 Troubleshooting & Support