Mitsubishi — 3.11 Functions of Special Auxiliary Relays and Special Registers

3 Functions of Devices in DVP-PM Function Group: Enabling External Input for X-Y Axis Number: D1875, D1955 Explanations: 1. When high byte of D1875 / D1955 = H’01, external input is enabled. When high byte of D1875 / D1955 = H’00 external input is disabled. 2. The low byte of D1875 and D1955 indicates the starting number of 4 consecutive external inputs (X), e.g., H’00 indicates X0 ~ X3 is to be enabled corresponding to JOG+, JOG-, MPG and ZRN. 3. Example: D1875 and D1955 = H’0110 refers to JOG+, JOG-, MPG and ZRN is enabled on X10 ~ X13. Function Group: Close-loop PID control (not supported by DVP-10PM) Number: D1877, D1878, D1880, D1882, D1888 Explanations: 1.

D1877 is the register for setting up close-loop PID control. The user can enable and select the feedback source of PID control system. 2. D1878, D1879: Set value (target value) of PID control. PID control system adjusts the output value to the set value by referencing the value from feedback source. 4. D1882, D1883: K I value, i.e. integral gain for close-loop PID control. 3. D1880, D1881: K P value, i.e. proportional gain for close-loop PID control. 5. D1888, D1889: The tolerable range for error(difference) between input and output value. The value set up in D1888 will limit the accumulated error within the tolerable range. 6. PID control diagram:

DVP-PM Application Manual 3-55 4 Operation pauses 5 Forward MPG input 6 Reverse MPG input 7 - Value of D1877 Feedback source 1 C200 2 C204 3 Current value (D1848、D1928、D2008) Other Disable close-loop PID control function