5 Categories and Use of Basic Application Instructions Explanations: 1. WDT instruction can be used to reset the Watch Dog Timer. If the PLC scan time (from address 0 to END or FEND instruction) is more than 200ms, the ERROR LED will flash. In this case, users have to turn the power OFF and then ON to clear the fault. PLC will determine the status of RUN/STOP according to RUN/STOP switch. If there is no RUN/STOP switch, PLC will return to STOP status automatically. 2. Time to use WDT: a) When error occur in PLC system. b) When the scan time of the program exceeds the WDT value in D1000. It can be modified by using the following two methods. i.
Use WDT instruction STEP0 END(FEND) WDT T1 T2 ii. Use the set value in D1000 (Default: 200ms) to change the time for watchdog. Points to note: 1. When the WDT instruction is used it will operate on every program scan as long as its input condition has been made. To force the WDT instruction to operate for only ONE scan, users have to use the pulse (P) format of the WDT instruction, i.e. WDTP. 2. The watchdog timer has a default setting of 200ms. This time limit can be customized to users requirement by editing the content in D1000, the wathdog timer register. Program example: If the program scan time is over 300ms, users can divide the program into 2 parts.
Insert the WDT instruction in between, making scan time of the first half and second half of the program being less than 200ms. 300ms program END Dividing the program to two parts so that both parts scan time are less than 200ms. 150ms program X0 WDT Watchdog timer reset 150ms program END DVP-PM Operation Instruction 5-20 API Mnemonic Function Controllers 20PM 10PM 07 WDT P Watchdog Timer Refresh Controllers 20PM 10PM OP Descriptions Program Steps N/A No operand. No contact to drive the instruction is required WDT, WDTP: 1 step